Why not use Fouling factor developed by TEMA for S&T in specifying Plate Heat Exchanger ?



Tubular Exchanger Manufacturers Association (TEMA) has developed a series of fouling factor for Shell and Tube (S&T). These fouling factor are generally higher than Plate Heat Exchanger (PHE), why not use S&T fouling factors to size PHE ?
Isn't this approach conservative and guarantee the performance ?

Reason being...

  • Oversized Plate Heat Exchanger (PHE) required extra CAPEX and extra Space for oversized PHE
  • Tubulence minimise fouling tendencies in correctly sized PHE. Oversized PHE results low actual velocity and increase potential fouling and inefficient heat transfer
  • HTRI studies showed PHE fouling significant lower than Shell & Tube Heat Exchanger (S&T)...factor of 6.7

GUIDELINE : Do not oversized PHE more than 25% against required area.

Further reading :